PROJECT HIGHLIGHTS
- Commissioned March, 2011
- Permit(s); Discharge
- 1/0.1/0.5 (TN/TP/Turbidity)
- Housing Development, Casino, School, Resort, Shopping Mall => River (Ruidoso River)
- MMF Capacity: 2.7 MGD
- Domestic WW, New Construction
- $11.85/gal
- 9 FTE (Full-Time Employee)

The new WWTP's use of the innovative membrane bioreactor technology will accomplish the required effluent discharge limits.
DESCRIPTION
The Ruidoso Downs, New Mexico MBR is located in the beautiful Rocky Mountains of south eastern New Mexico surrounded by the Lincoln National Forest. The plant services the housing, businesses, casino, a horse race track and ski resort with the purpose to meet the EPA requirements limiting phosphorus and nitrogen. The new limit of 0.1 mg/L of total phosphorus is accomplished with the Bio-P process that utilizes an internal recycle process across aerobic and anaerobic zones. The effluent is discharged into the Rio Ruidoso that is closely monitored to protect the fish and wildlife habitat. The technology involved in this design is intended to increase the biological nutrient removal while reducing chemical requirements to do so.
LOCATION
Ruidoso Downs, NM
IMAGES

PROJECT OVERVIEW
System Type(s) | Enviroquip ® MBR |
---|---|
Previous Facility Type | Aerobic Digestion, CAS, IFAS |
Owner | Village of Ruidoso |
Engineer | MolzenCorbin |
Contractor | RMCI |
Operations | Village of Ruidoso |
Delivery Method | Pre-Selection |
Time To Retrofit | 24 months |
Total Installed Project Cost | $32,000,000 |
PLANT DESIGN INFORMATION
Fine Screen Type | Band Screen |
---|---|
Aperture or Slot Size | 1 mm |
Supplemental Aeration Technology | Fine Bubble, Tubes & Disks |
MBR Blower Type | Positive Displacement |
Solids Management Data | Belt Press, Aerobic Digestion |
SCADA System | iFix |
Disinfection Method | UV |
# Process Stages | 6 |
MBR (MEMBRANE ZONE) DESIGN
Filtration Mode | PAG (Pump Assisted Gravity) |
---|---|
# of Reactors : | 6 |
Submerged Membrane Unit (SMU) | RW400 |
# SMU | 48 |
Design Flux (MMF) | 9.1 gfd |
Minimum Temperature | 8°C |
Peak Factor | 2.0 |
# of Maintenance Cleans | 4 |