PROJECT HIGHLIGHTS
Commissioned September, 2011
Commercial WW, Greenfield
Permit(s); Not Required
10/NA/NA (TN/TP/Turbidity)
Casino ⇒ Groundwater Recharge
MMF Capacity: 0.084 MGD
$28.57/gal
1 FTE (Full‐Time Employees)

The Ovivo system included a pre‐ piped, pre‐wired and pre‐tested equipment skid, which greatly reduced on‐site installation hours.
DESCRIPTION
Located in the North‐Central Wisconsin, the Stockbridge‐Munsee Community is a Band of the Mohican Tribe with over 1,500 members. As the tribal facilities continued to expand and with construction of the North Star Mohican Casino and Hotel already underway, the Stockbridge‐Munsee Community turned to Ovivo's MBR technology to upgrade and expand their aging recirculating sand filter treatment system. As good neighbors in the community and a strong desire to protect the environment, tribal leaders also required any new treatment technology to meet all State and Federal effluent standards for groundwater discharge including a stringent limit on Total Nitrogen of 10 mg/l.
LOCATION
Bowler, WI
IMAGES

PROJECT OVERVIEW
System Type(s) | Enviroquip ® MPAC® |
---|---|
Previous Facility Type | Recirculating Sand Filter |
Owner | Mohican Nation, Stockbridge-Munsee Band |
Engineer | MSA Professional Services |
Contractor | Heartland Construction |
Operations | Mohican Nation, Stockbridge-Munsee Band |
Delivery Method | Pre-Select, Pre-Purchase |
Time To Retrofit | 12 Months |
Total Installed Project Cost | $2,400,000 |
PLANT DESIGN INFORMATION
Fine Screen Type | Bar Screen |
---|---|
Aperture or Slot Size | 2 mm |
Supplemental Aeration Technology | Fine Bubble, Tubes |
MBR Blower Type | Positive Displacement |
Solids Management Data | Hauling |
SCADA System | Wonderware |
Disinfection Method | NA |
# Process Stages | 4 |
MBR (MEMBRANE ZONE) DESIGN
Filtration Mode | Pumped |
---|---|
# of Reactors : | 2 |
Submerged Membrane Unit (SMU) | RM200, KUBOTA® |
# SMU | 4 |
Design Flux (MMF) | 6.75 gfd |
Minimum Temperature | 5°C |
Peak Factor | 2.0 |
# of Maintenance Cleans | 4 |